| Conductor W x T | Cross-section | kA for 1 sec | kA for 3 sec |
| 38 x 5 | 190mm² | 33.4 | 19.3 |
| 38 x 6 | 228mm² | 40.1 | 23.2 |
| 40 x 3 | 120mm² | 21.1 | 12.2 |
| 40 x 6 | 240mm² | 42.2 | 24.4 |
| 50 x 3 | 150mm² | 26.4 | 15.2 |
| 50 x 4 | 200mm² | 35.2 | 20.3 |
| 50 x 5 | 250mm² | 44.0 | 25.4 |
| 50 x 6 | 300mm² | 52.8 | 30.5 |
| 50 x 6.3 | 315mm² | 55.4 | 32.0 |
| Conductor W x T | Cross-section | kA for 1 sec | kA for 3 sec |
| 12.5 x 3 | 37.5mm² | 6.6 | 3.8 |
| 20 x 1.5 | 30mm² | 5.3 | 3.0 |
| 20 x 3 | 60mm² | 10.6 | 6.1 |
| 25 x 1.5 | 37.5mm² | 6.6 | 3.8 |
| 25 x 3 | 75mm² | 13.2 | 7.6 |
| 25 x 6 | 150mm² | 26.4 | 15.2 |
| 30 x 3 | 90mm² | 15.8 | 9.1 |
| 30 x 5 | 150mm² | 26.4 | 15.2 |
| 38 x 3 | 114mm² | 20.1 | 11.6 |